Case Study: National Gypsum achieves energy optimization and data-driven maintenance with PointGuard

A PointGuard Case Study

Preview of the National Gypsum Case Study

How analytics helped to uncover the biggest wasters of energy use, and identify areas of improvement and equipment that needed upgrades

National Gypsum, a global board producer headquartered in Charlotte, NC, faced a complex HVAC and controls problem at its 73,400 sq ft headquarters: multiple brands and vintages of controls, broken components, faulty communications, and suboptimal settings that undermined energy efficiency and comfort. PointGuard was engaged to address these issues using Retro-Commissioning and ongoing building analytics services.

PointGuard’s team (with United Automation as controls contractor) performed benchmarking, trend analysis, testing, on-site reviews and staff interviews, then replaced chiller controls, enabled isolation valves, deployed a discharge air temperature reset algorithm, instituted an economizer for free cooling, and adjusted heating offsets by 4+ degrees to avoid excessive cycles. As a result, building analytics now maximize the value of the full-service maintenance agreement, allow National Gypsum to identify and prioritize repairs from data, ensure follow-through by the service provider, and deliver improved energy optimization and critical alerts for issues affecting the data center.